BACK

RMGW

Specifications

OBSOLET PRODUCT

alternative product RMGx series

Please consult the technical documentation for more information or contact AMRA.

 

  • Forcibly guided contacts (weld-no-transfer), test method according NF F62-002 (§12.3.10)
  • Instantaneous plug-in relays with 8 contacts, 12 A
  • Suitable for safety applications
  • Solid and rugged construction for intensive duty
  • Very high electrical life expectancy, exceptional endurance, optional magnetic arc blow-out
  • Self-cleaning knurled contacts
  • Manual operating lever
  • Wide variety of configurations and customizations
  • Wide range of sockets
  • Transparent cover, pull-out handle
  • Positive mechanical keying for relay and socket
Description

Very high performance relays with forcibly guided (weld-no-transfer), mechanically linked. Test method according to the standard NF F62-002 (§12.3.10).

A typical application is check reading of a contact to establish the position of the other contacts in self-monitoring control systems with absolute certainty.

8 changeover contacts, for exceptional application flexibility, with knurled finish to provide lower ohmic resistance thanks to the multiple electrical connection points: extended electrical life expectancy of the component, optimal performance for strongly inductive DC loads and for very low loads, such as in the case of interface signals.

Exceptional breaking capacity for controlling very heavy duty DC loads, also with intensive switching frequency. Optional magnetic arc blow-out for even higher breaking capacity.

Elevated production versatility. Available nominal voltage from 12 to 220VDC/440VAC. Facility to adapt the products to meet specific application requirements.

The excellent electrical and mechanical performance of these relays allows them to be used in the most demanding sectors, such as control and signalling functions in rail transport or in applications with continuous production processes. Suitable for use on rolling stock.

Compliance with standards
  • EN 61810-1, EN 61810-2, EN 61810-7 Electromechanical elementary relays
  • EN 60695-2-10 Fire hazard testing
  • EN 50082-2 Electromagnetic compatibility
  • EN 60529 Degrees of protection provided by enclosures
  • EN 60077 Electric equipment for rolling stock - General service conditions and general rules
  • EN 61373 Shock and vibration tests, Category 1, Class B
  • NF F62-002 (§12.3.10) Weld-no-transfer contacts, test method
  • EN 45545-2 Requirements for fire behaviour of materials and components – Product No. EL10 – Requirement R26, V0
  • ASTM E162, E662 Standard Test Method for Surface Flammability of Materials, Standard Test Method for Specific Optical Density of Smoke

Download technical drawings 2D/3D

LOGIN / REGISTRATION
PAIR320
  • Connection: Front
  • Terminal type: Spring clamp
  • Mounting: Panel /DIN Rail
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -50…+70°C

Details
96IP20-I DIN
  • Connection: Front
  • Terminal type: Screw
  • Mounting: Panel /DIN Rail
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -25…+70°C

Details
PRIR320
  • Connection: Rear
  • Terminal type: Spring clamp
  • Mounting: Panel
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -50…+70°C

Details
ADF4
  • Connection: Rear
  • Terminal type: Double faston
  • Mounting: Panel
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -25…+70°C

Details